Varec 4532 Bedienerhandbuch Seite 45

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 70
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 44
Varec, Inc. 35
4532 Operation and Description of Instrument Function
VH29 Upper Limit
Item type: read and write
Default value: 245°C
Range: -999.9°C ~ 999.9°C
Hi limit temperature alarm setpoint.
8.1.4 Element Position 1: VH30 ~ VH35
(VH36~VH39 is used only in 4539 ATC)
VH30 ~VH39 Position 1 ~ 6 (7~10 is used only in 4539 ATC)
Item type: read and write
Range: 0mm ~ 99999mm
Individual element position from tank bottom. Calculation is automatically performed
when element spacing "Even" is selected at VH85.
8.1.5 Element Position 2: VH40 ~ VH45 are not available in 4532 ATC
VH46 Hysteresis Width
Item type: read and write
Default: 10mm
Range: 0mm ~ 99999mm
Element switching point hysteresis. The hysterisis is an offset value added to the liquid
level when the level is increasing, and subtracted from the liquid level when the level is
decreasing. This setting ensures that the temperature value from an uncovered
temperature element is not used in calculating the average temperature.
VH47 Clear Memory
Item type: select
Default: None (0)
Selection: None, Clear
Reset matrix parameter to default setting.
Seitenansicht 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 69 70

Kommentare zu diesen Handbüchern

Keine Kommentare